CH 23 – Buildings

CHAPTER 23
BUILDINGS  

ARTICLE I
BUILDING CODE 

SECTION 23-1: BOCA CODE ADOPTED  

 There is hereby adopted by the Village of Lena for the purposes of establishing rules and  regulations for the construction, alteration, removal, demolition, equipment, use and occupancy, location  and maintenance of buildings and structures, including permits and penalties, that certain Building Code  known as the BOCA National Building Code 1996, is hereby adopted as reference thereto the same as if  fully set forth herein and the whole thereof, save and except such portions as are hereinafter deleted or  amended, three copies of which are on file in the office of the Village Clerk. Said Building Codes shall not  be applicable to the extent that it may conflict with the plumbing Code hereinafter set forth and the electrical  Code hereinafter set forth.  

SECTION 23-2: RESTRICTIONS  

 No building shall be constructed, altered, repaired or removed in violation of the Codes as herein  set forth.  

SECTION 23-3: INSPECTIONS/AGENCY DESIGNATED  

The President of the Village of Lena, with the advice and consent of the Board of Trustees, shall  designate a Building Inspector to assist in carrying out the inspections desirable to enforce the provisions of  this Article. The inspector shall send reports of its inspections to the Board of Trustees of the Village of  Lena for any necessary action.  

SECTION 23-4: APPLICATION/PERMIT REQUIRED  

 It shall be unlawful to construct, enlarge, alter or demolish a structure which is regulated by this  Code without first filing an application with the President of the Village of Lena or such persons as he may  designate in writing and obtaining the required permit therefore; except that ordinary repairs, as defined in  Section 104.1 of BOCA Basic Building Codes, which do not involve any violation of this Chapter shall be  exempt from this provision.  

SECTION 23-5: BUILDING PERMIT FEES  

 (A) No permit required by the Building Code Ordinance shall be issued until the fee prescribed in  Subsection (B) of this Section shall have been paid; nor shall an amendment to a permit be approved until  the additional fee, if any, due to an increase in the estimated cost of the building or structure, shall have  been paid.  

 (B) The fees for any permit required by the Building Code adopted heretofore by the Village of  Lena shall be in accordance with the Schedule of Fees set forth in 23-134. In the event that a building or  other improvement needing a Building permit is already under construction or has been completed at the  time of application for a Building permit, the fee shall be double the fee set forth above. 

1  

SECTION 23-6: COMPLIANCE  

 No building permit shall be issued by the Village to any individual who has failed to comply with any  outstanding Building permit issued to that person. Provided, however, that notwithstanding any other  provision herein, a Building permit may be issued to such individual to the extent necessary to bring any  building or structure within the Village of Lena into compliance with the Building Codes heretofore or  hereafter adopted by the Village.  

SECTION 23-7 through 23-16. RESERVED  

ARTICLE II  

PLUMBING CODE  

SECTION 23-17: THE ILLINOIS PLUMBING CODE ADOPTED  

 For the purpose of prescribing regulations governing the installation, alteration, repair and  maintenance of plumbing fixtures, lines and equipment, that certain document known as the Illinois  Plumbing Code, 1986, as amended through the date of the adoption of these codified ordinances,  promulgated by the Department of Public Health, State of Illinois, pursuant to authority granted by the  Illinois Plumbing License Law (ILCS Ch. 225, Act 320, Sections 0.01 et seq., as amended) is hereby  adopted as the Plumbing Code of the Village, save and except for such portions thereof as may be  amended or repealed in this subchapter.  

SECTION 23-18: DEFINITIONS  

 In addition to the definitions provided in the Illinois Plumbing Code, 1986, as adopted in Section  23-17, the following words and terms shall have the definitions given herein.  

“BLOW-OFF BASIN” A watertight receptacle provided to intercept the blow-off from the boiler and  condense the steam before entering a sewer.  

“CATCH BASIN” A watertight receptacle built to intercept waste water which may contain sediment from  surface, subsoil, gravel roof or stable drainage, grease or oils, or from steam or hot water boilers before  overflowing into a sewer or drain.  

“HOUSE SEWER” The sewer which begins three feet outside of the foundation wall of a building and  connects the house or building drain with the main sewer, or with a septic tank or cesspool on the premises.  

“MAIN SEWER” The main sewer which is connected with the general sewerage system of the Village.  

“PLUMBER” A person who is the holder of a license duly issued in accordance with the provisions of the  Plumbing License Law of Illinois, designating such person as a “licensed plumber”.  

“PRIVATE SEWER” Any main or branch sewer located either on public or private property, not  constructed or accepted by the Village, which conveys the drainage of one or more buildings or sites to the  sewer system of the Village, or its outlet.  

“SEWER” All work and material in installing, connecting or repairing any system of drainage whereby foul,  waste of surplus matter is discharged through a pipe from a building or fixture to the main sewer, or to any  other point of disposal. 

2  

SECTION 23-19: FILE COPIES  

 Three copies of the Illinois Plumbing Code, 1986, as adopted in Section 23-17, shall be kept on file  in the office of the Village Clerk, and there kept available for public use, inspection and examination.  

SECTION 23-20 through 23-33. RESERVED  

ARTICLE III  

ELECTRICAL CODE 

SECTION 23-34: STANDARDS AND SPECIFICATIONS ADOPTED  

 There are adopted, as safe and practical standards for the installation, alteration, and use of  electrical equipment in the Village, the rules and regulations of the National Fire Protection Association of  electrical wiring and apparatus, contained in the code known as the National Electrical Code of 1996 (as  amended from time to time), except such portions as hereafter modified, or amended, a copy of which code  is now on file in the office of the Village Clerk, the Electrical Inspector, and the Building Inspector, and the  same are adopted and incorporated as fully as if set out at length herein, and from the date on which this  section shall take effect the provisions thereof shall be controlling within the limits of the Village and the  National Electrical Code of 1996 and the amendments thereto adopted shall be known as the Electrical  Code.  

SECTION 23-35: AMENDMENTS TO THE NATIONAL ELECTRICAL CODE ELECTRICAL SERVICE   (A) Residential new service shall be in metal conduit or approved PVC only.   (B) Commercial or industrial new service shall be in metal conduit only, PVC not allowed.  

 (C) Apartment, duplexes, town houses, condos, and multifamily new service and subpanels shall  be in metal conduit only, PVC shall not be allowed.  

 (D) For minimum service, use 100 amp. 16 circuit breaker cabinet with 100 amp main breaker.  The minimum breaker panel size for 200 amp service shall be 30 space.  

 (E) Service run over four (4) feet into a home or building shall have approved disconnect.  

 (F) Service on pole or outside run to main cabinet or subcabinet shall also have main breaker or  disconnect inside at cabinet also.  

 (G) Two separate eight (8) foot ground rods placed at least six (6) feet apart. Ground wire to come  out the side of the meter base, inside of the conduit and connect to ground rod with ground clamp with hub.  Ground wire goes to terminal at meter socket and on into terminal in breaker panel, bonding bushings  required around concentric or eccentric knockouts.  

 (H) Ground clamp to be six (6) inches above grade.  

 (I) Power underground wires to be inspected before ditch is covered.  

 (J) Service shall be grounded to a metallic cold water pipe and to a supplementary electrode.  Water meter requires a bonding jumper.  

 (K) Underground meter pedestal shall be secured to a treated wooden 4×4 post secured in cement  at least four (4) feet in the ground for mobile home insulation (installation).  

 (L) Minimum 100 amp service will be #3 copper and 1 ¼ -inch conduit. 

3  

 (M) Minimum 200 amp service will be #3/0 copper, and 2-inch conduit.  

 (N) At no time shall aluminum wire ever be used as service entrance conductors.  

 (O) Dwellings that have an area greater than 1,800 square feet shall have a minimum service  rating of 200 amps. NOTE: Square-feet includes dwelling garages and in some cases basement and  bathroom is roughed in and egress windows installed in basement.  

 (P) New multifamily units over two (2) units, town houses and apartments shall be in metal conduit.  SECTION 23-36: ENTERANCE CABLE  

 Entrance cable shall not be used for service or electric stove runs. The use of service entrance  cable will only be approved by the inspector in some farm building applications.  

SECTION 23-37: TYPE OF WIRING  

 (A) Romex with a bare conductor for equipment.  

 (B) Romex to be stapled 6 inches from outlet and every three (3) feet.  

 (C) In the basement and garage, exposed wiring to be in conduit, basement, upper runs drop to  box and use conduit. In basement and garage, wiring to be covered by drop ceiling or drywall.  

NOTE: Insulation will no longer be a means of cover.  

 (D) Metal buildings and metal sheds shall be done in conduit only. Commercial, farm, agricultural,  and industrial buildings shall be in metal conduit only. All dwellings or structures exceeding three (3) floors  above grade shall be in metal conduit only.  

 (E) The use of electrical nonmetallic tubing (ENT) shall be prohibited in commercial, residential,  industrial and all applications.  

 (F) All agricultural buildings shall be in metal conduit.  

 (G) Termination at permanently installed wiring devices shall be of the binding head screw, screw  tightened clamp, set screw or manually torque hardware.  

 (H) Premises wiring methods utilized for component interconnection, box dimensions, and  enclosures shall not be allowed in dwelling occupancies. Surface wiring methods listed and otherwise  approved by the N.E. Code may be allowed. Terminations at permanently installed wiring devices shall be  of the binding head screw, screw tightened clamp, set screw or manually torque hardware. Splices and  taps shall be installed by methods in compliance with provisions of Article 110 and other applicable articles  of the N.E.C.  

 (I) Mobile homes shall conform to current National Electrical Code and current Lena Code.   (J) Switches, devices and fixtures to be rated according to conductor size.   (K) Garage receptacles on 20 amp separate circuit with 20 amp GFI rated receptacles.  

 (L) The refrigerator or freezer or central vacuum to be single receptacle and does not have to be on  a GFI. 

4  

 (M) One (1) 20 amp outside GFI receptacles required. 1996 code requires all below grade,  basement receptacles to be on ground fault.  

 (N) Basement to be on separate circuit lights also.  

 (O) Laundry equipment and sump pump to be on a single receptacle and not on a GFI circuit.  Industrial and commercial to comply with ground fault requirements of the Village.  

CIRCUITS AND REQUIRED OUTLETS  

 (A) Receptacles and lights eight (8) openings on #14 wire use 15 amp breaker; ten(10) openings  on #12 wire use 20 amp breaker.  

 (B) Install one (1) wall switch to control light outlet in every room, hallways, stairways, garage, and  outdoor entrances.  

 (C) Identify circuits in cabinet.  

 (D) In each room duplex outlets shall be installed so that no point along the wall is more than six (6)  feet from an outlet, including any space two (2) feet or more.  

 (E) Industrial and commercial outlet to be rate for 20 amps. 20 amp circuit, #12 wire, 20 amp  device.  

 (F) One (1) outlet needed within three (3) feet of water softener rough-in site.  SPLICES AND CONNECTIONS  

 (A) Wires shall be twisted and mechanically secured with wire nuts.  

 (B) Romex must be stripped before putting in boxes.  

 (C) All receptacles to be bonded.  

 (D) No more than two (2) wires will be allowed on each side of receptacle.   (E) Joints are to be made up for rough-in inspection.  

LAUNDRY  

 (A) One (1) twenty-amp circuit for receptacle, receptacles to be rated 20 amp.  KITCHEN  

 (A) Lighting to be on one (1) circuit, dishwasher on one (1) circuit, receptacles shall be on two (2)  20 amp circuits, receptacles to be rated 20 amp. Receptacle to be installed on each counter space wider  than twelve (12) inches.  

 (B) Microwave to be on a separate 20 amp circuit.  

GARAGE  

 (A) One (1) twenty-amp circuit with receptacles rated 20 amp.  

 (B) One receptacle required for the garage door opener. 

5  

 (C) Each finished and unfinished wall in garage is to have two (2) 20 amp receptacles on a GFI.  CLOSETS  

 (A) Closets less than 3-foot depth will need to have approved closet fixtures if light is installed.  BASEMENT  

 (A) Finished walls to have a receptacle every twelve (12) feet of wall space.   (B) Electrical panel to have a light adjacent to it, within four (4) feet of panel.  GROUND-FAULT CIRCUIT  

 (A) Bathroom lights over tub in shower stalls to be on GFI. Bar light over sink is contractors option.   (B) Bathrooms, saunas, swimming pools, garages and outside receptacles on ground-fault.   (C) Device box to have proper amount of cubic inches for wires and ground-fault receptacle.   (D) Garage door opener outlet does not have to be on a ground-fault.  

 (E) 1996 N.E.C. Rules on GFI’s for kitchen areas.  

 (F) GFI receptacles below grade to be on a GFI except laundry, sump pump and central vacuum  which have to be single receptacle.  

BOXES  

 (A) Wiring device boxes shall have sufficient cubic inches for wires installed.  

 (B) Approved metal boxes shall be required for all ceiling boxes in dining room, living room,  kitchen, family room, offices, bedrooms and all habitable rooms.  

 (C) Commercial and industrial bathrooms accessible to the public to have emergency lights  installed.  

 WATER PUMP, FURNACE AND AIR CONDITIONER  

 (A) Furnace and air conditioner shall disconnect switch for the appliance.  

 (B) Water pump shall have disconnect switch if not in same room as breaker panel and if over  twelve (12) feet from the panel.  

MSCELLANEOUS  

 (A) All can lights shall be IC or double housing type for residential use.  

 (B) Electrical contractors will have circuits identified for the final inspection.  

 (C) Electrical contractors are to have their business identification on the meter socket and on the  main breaker panel; example: Name, phone number and house number.  

 (D) All homes under construction shall have addresses and Lot Numbers visible to inspectors from  the road at all times. 

6  

NOTE: Lift stations, sewer injector pumps have to be on a 20 amp separate circuit. In waste is used  through the system it must have an alarm wired into the circuit to show when power fails. (77 Ill. Admin.  Code IDPH Requirements)  

 MOBILE HOMES  

 (A) The connection from the distribution panels in a mobile home to the power source shall be  made with a proper conduit which has been approved by the Village.  

 (B) In addition, each mobile home shall have an approved grounding system to the shell and metal  framework.  

 (C) Mobile homes shall conform to all Village and county electrical codes.   (D) Approval of electrical before occupancy.  

SMOKE ALARMS  

 (A) To be installed in hallways, basement areas, on all levels and in all bedrooms and sleeping  areas. Smoke alarms are to be hardwired 120 bolt interconnected with battery backup. This applies to all  residential, multi-family and apartment units. This also includes new construction and new remodeling.  

 (B) Commercial and industrial to have alarm systems or hardwired 120 volt interconnected battery  backup smoke detectors.  

 (C) New and old multi-family, apartment, commercial and industrial buildings to have emergency  lights and exit lights installed where deemed necessary by the Building, Electrical and Fire Department  officials.  

SECTION 23-38 through 23-51. RESERVED  

ARTICLE IV  

MECHANICAL CODE  

SECTION 23-52: THE BOCA NATIONAL MECHANICAL CODE ADOPTED  

 For the purpose of prescribing regulations governing mechanical systems, that certain document  marked and designated as the BOCA National Mechanical Code, eighth edition (1993), as promulgated by  Building Officials and Code Administrators International, Inc., is hereby adopted as the Mechanical Code of  the Village of Lena, save and except for such portions thereof as may be amended or repealed in this  subchapter.  

SECTION 23-53: FILE COPIES  

 Three copies of the BOCA National Mechanical Code, as adopted in Section 23-52, shall be kept  on file in the office of the Village Clerk and there kept available for public use, inspection and examination.  

SECTION 23-54 through 23-69. RESERVED 

7  

ARTICLE V  

MAINTENANCE CODE  

SECTION 23-70: ADOPTION OF PROPERTY MAINTENANCE CODE  

 That a certain document, three (3) copies of which are on file in the office of the Village Clerk of the  Village of Lena being marked and designated as “The BOCA National Property Maintenance Code”, 1993,  be and is hereby adopted as the Property Maintenance Code of the Village of Lena, in the State of Illinois;  for the control of buildings and structures as herein provided; and each and all of the regulations, provisions,  penalties, conditions and terms of said BOCA National Property Maintenance Code are hereby referred to,  adopted, and made a part hereof, as if fully set out in this Ordinance, of which 3 copies are on file with the  Village Clerk.  

SECTION 23-71 through 23-80. RESERVED  

ARTICLE VI  

ONE & TWO FAMILY DWELLING CODE  

SECTION 23-81: CODE ADOPTED  

 The One and Two Family Dwelling Code, 1995, as recommended by the Building Officials and  Code Administrators International, Inc. is hereby adopted by reference thereto as though set fourth fully  herein and the whole thereof, save and except those provisions as are hereinafter deleted, modified or  amended, three copies of which are on file in the office of the Village Clerk of Lena, Illinois for use and  examination by the public.  

SECTION 23-82 through 23-91. RESERVED  

ARTICLE VII  

BOCA NATIONAL FIRE PROTECTION CODE  

SECTION 23-92: CODE ADOPTED  

 For the purpose of prescribing regulations governing the construction of buildings and procedures  for the general safety and protection of the public from fire, smoke, and related hazards, that certain  document known as the BOCA National Fire Protection Code, 1996 edition, as promulgated by Building  Officials and Code Administrators International, Inc., is hereby adopted as the Fire Code of the Village, save  and except for such portions thereof as may be amended or repealed in this subchapter.  

SECTIONS 23-93: APPLICATION OF CODE  

 The BOCA National Fire Protection Code, as adopted in Section 23-92, shall be applicable to all  buildings, structures and improvements in the Village.  

SECTION 23-94: FILE COPIES  

 Three copies of the BOCA National Fire Protection Code, as adopted in Section 23-92, shall be  kept on file in the office of the Village Clerk and there kept available for public use, inspection and  examination.  

SECTION 23-95: CONFLICT OF LAWS  

 (A) In the event of a conflict between any of the provisions of the BOCA National Fire Protection  Code, as adopted in Section 23-92 and any provision of these codified ordinances, or any other local  ordinance or resolution, the local ordinance shall control. 

8  

 (B) In the event of a conflict between any of the provisions of such code and a provision of any  other technical code adopted or referred to by the Village as a standard, the higher or stricter standard shall  control.  

SECTION 23-96: VIOLATIONS; ABATEMENT; SEPARATE OFFENSES  

 (A) No person shall erect, use, occupy or maintain any building or structure in violation of any  provision of the BOCA National Fire Protection Code, as adopted in this Article, or cause, permit or suffer  any such violation to be committed.  

 (B) It is the responsibility of the offender to abate the violation as expeditiously as possible, and  each day during which such violation is permitted to continue shall constitute a separate offense.  

SECTION 23-97: RESPONSIBILITY FOR VIOLATIONS  

 In the case of a person, firm or corporation employing a contractor, both the employer and the  contractor shall be responsible for all violations under this subchapter. For purposes of this subchapter,  “employer” shall be defined as anyone contracting for the performance of work for hire, whether the person  so employed is deemed an employee, independent contractor, agent, or otherwise.  

SECTION 23-98 through 23-109. RESERVED  

ARTICLE VIII  

ILLINOIS BOILER AND PRESSURE VESSEL SAFETY ACT  

SECTION 23-110: ACT ADOPTED  

 For the purpose of prescribing regulations governing the installation, construction, alteration, repair  and maintenance of boilers, except such boilers as are exempt under the code, that certain document  known as the State of Illinois, Office of the State Fire Marshal, Division of Boiler and Pressure Vessel  Safety, Boiler and Pressure Vessel Safety Act and Rules and Regulations, 1992 edition, as formulated and  published by authorization of the State Board of Boiler and Pressure Vessel Rules, is hereby adopted, save  and except for such portions thereof as may be amended or repealed in this subchapter.  

SECTION 23-111: APPLICATION OF ACT AND RULES AND REGULATIONS  

 The Boiler and Pressure Vessel Safety Act and Rules and Regulations, as adopted in Section  23-110, shall apply to the installation, construction, maintenance and repair of all boilers covered by such  Act and Rules and Regulations. The construction, installation, maintenance and repair of all boilers exempt  under such Act and Rules and Regulations shall be governed by the pertinent provisions of Sections 23-17  through 23-33, and the Illinois Plumbing Code, as adopted therein, shall apply to and govern the  installation, repair and maintenance of all water or steam lines, for heat distribution purposes, connected to  a water or steam boiler, whether such boiler is subject to, or exempt from, the Act and Rules and  Regulations.  

SECTION 23-112: FILE COPIES  

 Three copies of the Boiler and Pressure Vessel Safety Act and Rules and Regulations, as adopted  in Section 23-110, shall be kept on file in the office of the Village Clerk, and there kept available for public  use, inspection and examination. 

9  

SECTION 23-113 through 23-124. RESERVED  

ARTICLE IX  

PERMITS AND FEES  

SECTION 23-125: PERMIT REQUIRED  

 No person shall perform any construction, installation, repair or maintenance for which a permit is  required as provided in this Building Code without an appropriate permit being used.  

SECTION 23-126: PERMIT APPLICATIONS; PAYMENT OF FEES  

 Before any permit is issued, the applicant shall submit to the Building Inspector, on appropriate  forms, a detailed statement of the specifications and other information, including cost estimates, as the  Building Inspector may reasonably require. The application shall also set forth the name of the owner, the  address of the property and the name of the contractor. The full permit fee shall be paid at the time of filing  the application.  

SECTION 23-127: ISSUANCE OF PERMIT  

 If the Building Inspector determines that the application is in proper form and that the plans and  specifications are in accordance with the applicable ordinances and statutes, the Building Inspector shall  issue the permit. No permit shall be issued if the applicant is delinquent in other fees or monies owing to the  Village. If a permit is denied, the Building Inspector shall state in writing the specific reasons why the permit  is denied.  

SECTION 23-128: DURATION OF PERMITS  

 A permit shall be effective for one year from its date of issuance only, unless a longer time is  granted in the permit. Commencement or work shall be made within one year. For any construction,  erection, enlarging, remodeling, altering or repairing of any wall, structure, building or part thereof for which  a permit is required and for which the permit fee is $15.00 or less, the exterior of the project shall be fully  completed within one year after commencement of the work, provided that if such work is not completed  within the one-year time period, and if application is made, a second permit may be issued granting an  additional year from the date of issuance for such completion.  

SECTION 23-129: COMPLIANCE REQUIRED  

 All work under a permit shall comply strictly with the terms of the permit, with the application, plans,  specifications and other data upon which the permit is based and with the applicable provisions of this  Building Code.  

SECTION 23-130: ISSUANCE OF PERMITS NOT AN APPROVAL OF VIOLATIONS  

 The issuance of a permit shall not be construed as approval or waiver of any violation of this  Building Code or any other law. It shall not be the responsibility of the Building Inspector to review the  application for compliance with any applicable zoning regulation. 

10  

SECTION 23-131: AMENDMENTS TO PLANS AND SPECIFICATIONS AFTER PERMIT ISSUANCE;  SUPPLEMENTARY PERMITS  

 If it is found necessary to make any changes to the plans and specifications upon which a permit  has been issued, amended plans and specifications shall be submitted and a supplementary permit may be  issued to cover the change. No person, other than the Building Inspector, shall change or alter the wording  of any permit.  

SECTION 23-132: TRANSFER OF PERMITS  

 Permits shall not be assignable or transferable without the written consent of the Building Inspector,  either as to property for which they are issued or as to the permittee to whom they are issued.  

SECTION 23-133: FEE EXEMPTIONS  

 (A) Tax supported or tax exempt organizations. Work performed for any tax supported or tax  exempt organization shall be exempt from the payment of a permit fee as required in the Building Code.  

 (B) Emergencies. In an emergency, when the situation demands immediate action for the  protection of life or property, and obtaining a permit prior to the construction, installation or repair is  impossible, any contractor may start such work without first obtaining a permit. However, the contractor  shall make application for and obtain such permit as soon as possible, and in no event later than three days  after the work is performed.  

 (C) Minor repairs. No permit shall be required for minor repairs or alterations which do not involve  structural changes, installation of new units or connections and which do not exceed $100.00 as the price  charged the owner.  

SECTION 23-134: BUILDING PERMIT FEES  

 (A) The fees to be charged for building permits shall be based on the following schedule:  

 New House……………………………………………………. $90-$300   New Commercial……………………………………………… $150-$500   Garages……………………………………………………….. $30-50   Utility sheds…………………………………………………… $25  

 House addition………………………………………………… $30  

 Commercial addition…………………………………………. $150-$250   Demolish………………………………………………………. $25  

 Decks, patio, porch, signs…………………………………… $25  

 Driveways, retaining walls…………………………………… $25  

 Driveway pillar………………………………………………… $25  

 Fence………………………………….……………………….. $25 

11  

 (B) The building square footage for determining fees shall be:   (1) House  

 0-1000…………………………………………………………. $ 90   1001-1500…………………………………………………….. $125   1501-2000…………………………………………………….. $150   2001-3000…………………………………………………….. $200   Over 3000………….………………………………………….. $300  

 (2) Garage  

 0-550………………………………….…………………..….… $30   Over 551…………….……………………………….….….….. $50  

 (3) Commercial  

 0-5000……………..…………………………………………… $150   5001-15,000……..……………………………………….……. $250   15,001-30,000………………………………………………… $350   Over 30,000…………………………………………………… $500  

 (4) Commercial addition  

 0-5000…………………………………………………………. $150   Over 5000……………….…………………………………….. $250  

ARTICLE XIII  

DANGEROUS BUILDINGS  

[GET CITY OF ROCKFORD CODE]  

ARTICLE XIX  

ADMINISTRATION AND ENFORCEMENT  

[REFERENCE ACCORDING TO ILCS] 

12  